Kinetico 2050c

Kinetico 2050c
  • Through its design Kinectico 2050c does not have the drawbacks, which electrical systems has.
  • The filter is designed to operate under the "Twin" scheme, where system consists of two columns with filtering material. Softened water is used for washing the ion exchange resin, that provides a higher washing efficiency and significantly reduces water and salt consumption for the process and prolongs the life of the filter.
  • The system does not need to be connected to the power supply! It eliminates the risk of electric shock, the probability of failure of the microprocessor and other problems.
  • The system operates on the counter. Salt and water are used for regeneration only when resin resource in one of the columns has ended. Thereby the possibility of delayed filter washing is excluded.
  • The filter is resistant to corrosion.

Technical characteristics

Model 2050c
Maximum allowable concentration of hardness (mg/l) / ppm 16 / 800
Maximum allowable concentration of ferrous iron, mg/l 0 - 0.5
Minimum pH, (standard units) 3 - 12
Regeneration type Backflow
Type and number of filling Filtering environment: Small resin – 11 l х 2 sandwiched layer of cation
Minimum/Maximum water temperature °C 2 - 49
Performance minimum / maximum 22 - 45 l/min
Water consumption for regeneration in liters 27
Time for regeneration in minutes 11
Salt consumption per regeneration,(2 settings) kg 2.7 - 4.5
Maximum amount of salt in the salt compartment 25 kg
Dimensions of the salt tank diameter/height -
The pressure drop at the operating expense, atm up to - 0.5
Maximum flow rate in drain pipeline during regeneration - reverse flushing, l/min. 0.60
Minimum/Maximum water pressure for washing, bar 2.5 - 8.5
Dynamic pressure 1 - 8.5
Regeneration frequency by counter (1.1 - 94 l/min polypropylene turbine)
Filter height, сm 69
Base area, width, depth, сm 29 х 68.7
Electrical characteristics None
Filter weight (shipping / in use), kg 41 / 54
Connection for water pipe «3/4» inch, external thread with clips (standard for pipes)

Requirments for the raw water

Water hardness, mg/l (ppm) < 16 / 800
Ferrous iron content, mg/l < 0 - 0.5
Three-valent iron content, mg/l < 0
Manganese content, mg/l < 1
3 - 12
Free chlorine Cl2 content, ml/l < 0.5
Oil product content, mg/l < 0.5

Attention: Water softener Kinetico 2050c does not clear the water from the iron while it is in the organic complexes, hydrogen sulfide, bacterial contamination, oil products and organic substances.

Equipment

Softener assembly 1 piece
Overflow fitting 1 piece
Drain fitting 1 piece
Drainage tube D = 12 mm (1/2”), L = 1.5 m 1 piece

Gallery